Distance protection

<< Click to Display Table of Contents >>

Navigation:  Components and parameters > Switches and protections >

Distance protection

The distance protection measures the impedance in the direction of the feeder. There are three zones with forward directional sensitivity and one zone with backward directional sensitivity.

 

The distance protection is a part of the Circuit Breaker.

 

 

PARAMETERS

 

Parameter

Default

Unit

Description

Type

 

 

Predefined type from component database

Short

 

 

Short name. Maximum 10 characters.

t,input

0

s

Pickup time

t,output

0

s

Operation output time

 

 

 

 

Pickup

 

 

 

Ie >

0

A

Earth current activation threshold value

I >

0

A

Overcurrent activation threshold value (pick-up current)

U <

0

kV

Undervoltage activation threshold value

Z <

0

Ohm

Impedance zone activation threshold value

 

 

 

 

Kn

0

 

Factor KN for asymmetric short circuits: absolute value and angle

 

 

 

 

Forward:

 

 

 

Number of zones

0

1/2/3

Number of zones (1, 2 or 3)

t1, t2, t3

0

s

First, second and third zone tripping time

end time

0

s

Forward directional final  tripping time

 

 

 

 

Backwards:

 

 

 

T

0

s

Reverse directional tripping time

 

 

 

 

Undirected:

 

 

 

end time

0

s

Undirected final tripping time

 

Edit zone

Using the button Edit zone the characteristics of the three forward directional zones and the one reverse directional zone can be specified.

 

Parameter

Default

Unit

Description

Number of characteristic

1

1/2

1: for all fault types the same characteristic

2: different characteristics for phase-phase fault and phase-ground fault

Characteristic

 

 

Circle / Mho / Polygon

 

 

 

 

Circle:

 

 

 

Z

0

Ohm

Circle radius

 

 

 

 

Mho:

 

 

 

Z

0

Ohm

Circle radius

R

0

Ohm

Circle centre R-coordinate

X

0

Ohm

Circle centre X-coordinate

 

 

 

 

Polygon (max 5 lines):

 

 

 

R

0

Ohm

R-coordinate of a point on the line

X

0

Ohm

X-coordinate of a point on the line

Direction

0

degrees

Slope angle of the line through the point R-X

 

 

 

 

Circle

A zone can be characterized with a circle diagram. The forward-facing zones 1 and 2 are provided with auxiliary buttons with the default of 85% and 115% for filling in the impedance. These values can be adjusted by right-clicking on them. For zone 1 there is then a choice of 70, 75, 80, 85, 90 and 95%. For zone 2 there is then a choice of 105, 110, 115, 120, 125, 130 and 85 (+85 ')%.

With the 85% button at Z1, the value of 85% of impedance in the forward direction to the next node can be transferred to the input field of Z1.

With the 115% button at Z2, the value of 115% of impedance in the forward direction to the next node can be transferred to the input field of Z2.

85 (+ 85 ')% means: 85% of impedance in the forward direction to the next node + 85% of impedance of the shortest non-mesh cable from that node.

 

Mho

A zone can be characterised using a circle diagram of which the centre is moved in the R-X plane. The circle radius is indicated with the impedance Z and the centre with R and X (in Ohm).

 

Polygon

A zone can be characterised using a polygon. It is defined by 3, 4 or 5 lines, crossing each other in such a way that they enclose an area. Each line is defined with a point where it runs through and a slope (in degrees).

 

 

MODELLING

 

Three zones of the impedance relay have a forward measurement, one zone has a reverse measurement. The final zone has the possibility of only a forward directional measurement or also a reverse directional measurement. If the reverse directional measurement is not to be used, the corresponding tripping time (undirected end time) must have a value of 0.

 

Circle characteristic

Distantiebeveiliging 1

The forward directional measurement only lead to a trip if the measured impedance is located in the grey shaded area in the above figure. The slope of the slanted line in the R-X diagram is -45 degrees.

 

The next table applies:

 

Measured impedance

Action

|Zm| < Z1 and Zm in grey area

Trip on t = t1 s

|Zm| < Z2 and Zm in grey area

Trip on t = t2 s

|Zm| < Z3 and Zm in grey area

Trip on t = t3 s

|Zm| > Z3 and Zm in grey area

Trip on t = forward directed final time

|Zm| < Zreverse and Zm not in grey area

Trip on t = reverse time

Zm not in grey area

Trip on t = undirected final time

 

For the zone impedances the following applies:

Z1 < Z2 < Z3

 

Mho characteristic

The forward directional measurement only lead to a trip if the measured impedance is located in the grey shaded area in the above figure. The slope of the slanted line in the R-X diagram is -45 degrees.

 

The zones are described by the circles, using the centre points (M1, M2) and their radii (Z1, Z2).

Distantiebeveiliging 2

The next table applies:

 

Measured impedance

Action

Zm inside circle 1 and Zm in grey area

Trip on t = t1 s

Zm inside circle 2 and Zm in grey area

Trip on t = t2 s

Zm inside circle 3 and Zm in grey area

Trip on t = t3 s

Zm outside circle 3 and Zm in grey area

Trip on t = forward directed final time

Zm inside reverse circle and Zm not in grey area

Trip on t = reverse time

Zm outside reverse circle and Zm not in grey area

Trip on t = undirected final time

 

For the zone impedances the following applies:

Z1 < Z2 < Z3

 

Polygon characteristic

The forward directional measurement only lead to a trip if the measured impedance is located in the grey shaded area in the above figure. The slope of the slanted line in the R-X diagram is -45 degrees.

The zones are described by the polygons, using the lines through the points Z0, Z1, Z2, Z3 and the angles of their slopes.

 

Distantiebeveiliging 3

The following table applies:

 

Measured impedance

Action

Zm inside polygon 1 and Zm in grey area

Trip on t = t1 s

Zm inside polygon 2 and Zm in grey area

Trip on t = t2 s

Zm inside polygon 3 and Zm in grey area

Trip on t = t3 s

Zm outside polygon 3 and Zm in grey area

Trip on t = forward directed final time

Zm inside polygon circle and Zm not in grey area

Trip on t = reverse time

Zm outside polygon circle and Zm not in grey area

Trip on t = undirected final time

 

For the zone impedances the following applies:

Z1 < Z2 < Z3

 

Measurement for diverse fault types

For asymmetrical phase to ground fault the factor KN is introduced. In those cases a zero sequence current I0 flows. The following applies:

 

 

or

 

 

where:

 

 

For a three phase fault:

 

 

 

 

 

For a two phase fault (e.g. phases b and c)

 

 

 

 

 

For a two phase to ground fault (e.g. with phases b and c)

 

 

 

 

For a single phase to ground fault (e.g. phase a)