<< Click to Display Table of Contents >> Navigation: Components and parameters > Switches and protections > Differential protection |
Differential protection is part of a circuit breaker and also refers to other circuit breakers and/or measurement fields, the other measuring points. In this way, an arbitrary object (rail, transformer, cable) or an arbitrary set of objects (direction) can be secured with the differential protection. The differential protection operates when the corresponding circuit breakers are no more than six branches apart. In that case the correct flow direction and transfer ratio of a possible intermediate transformer is taken into account.
Only this circuit breaker is tripped. Not the circuit breakers at the "other measurement points".
PARAMETERS
Parameter |
Default |
Unit |
Description |
Type |
|
|
Type name of the differential protection |
t,input |
0 |
s |
Pickup time |
t,output |
0 |
s |
Operation output time |
Sort |
|
|
Sort |
m |
|
|
factor m (Time Multiplier Setting), at inverse characteristic |
Other measurement points |
|
|
List of circuit breakers and measurement units connected to this differential protection |
dI > |
0 |
A |
First threshold value for activating the differential protection |
t > |
0 |
s |
Time for trip signal |
dI >> |
0 |
A |
Second threshold value for activating the differential protection |
t >> |
0 |
s |
Time for trip signal |
k1 |
0 |
|
Factor k1 |
k2 |
0 |
A |
k2 |
k3 |
0 |
|
Factor k3 |
k4 |
0 |
A |
k4 |
Release by the first current protection |
no |
|
The current has also to be bigger then I> of a fixed time characteristic |
No own measurement |
|
|
The circuit breaker itself does not provide a measurement |
The operation is as follows. Suppose two currents I1 and I2 (as complex values) are measured, both directed towards the object to be protected. In the normal situation both flows are equal but opposite to each other: I1 = - I2. The absolute value of the sum of the measured flows Diff is then equal to zero.
Diff = | I1 + I2 |
In the event of a short-circuit in the object to be protected, Diff is no longer equal to zero, as there is current flowing from the object to the ground. If Diff is greater than the threshold value dI> for a time of at least t> a trip command will be given.
k1, k2, k3, k4
The values k1, k2, k3, k4 are used as an extra tripping criterions. Suppose that two currents I1 and I2 are measured as complex values. The sum of the absolute values will be calculated as follows:
Sum = | I1 | + | I2 |
The differential protection will only trip if the following three conditions are met:
Diff > dI>
Diff > k1 ? Sum + k2
Diff > k3 ? Sum + k4