Unbalanced load flow

<< Click to Display Table of Contents >>

Navigation:  Calculations >

Unbalanced load flow

The power system is a three-phase system. In the high and medium voltage networks, the majority of the load are three-phase symmetrical loads. In some cases, such as with the supply of the railways, the load is connected between two phases. In low-voltage networks, most of the connections are single phase connections. The aim is to distribute all single-phase loads in such a way that the three phases are loaded as equally as possible. As a result, the voltage in the distribution grid will be mostly three-phase symmetrical. The deviation of the three phase voltages with respect to the three-phase symmetry is indicated by the asymmetry. The asymmetry is visible if in a three-phase system the effective values ​​of the voltages of the three phases are not equal to each other or are not shifted by 120 degrees relative to each other.

 

Asymmetry is caused by non-symmetrical loads. This is the case, for example, when single-phase loads are not properly distributed over the different phases of a three-phase connection. But also cause by heavy loads between two phases

 

See:

General

Calculation

Result