IEC 60909: Result

<< Click to Display Table of Contents >>

Navigation:  Calculations > IEC 60909 >

IEC 60909: Result

Network

After performance of an IEC 60909 calculation, results are shown on the basis of a View.

Only if an IEC 60909 calculation is carried out for one selected node can all supply branch and element currents be stated in the network.

The functionalities available with the menu item Results will be explained successively below.

 

General

With Calculate | Results | Survey an overview of the results for all nodes and branches for which an IEC 60909 calculation has been carried out will be displayed. The results are shown for nodes and branches in two lists.

 

Nodes

node

Unom

Sk"

Ik"

Ip

Ri and Xi

R/X

Name of node

Nominal voltage of the node

Subtransient short-circuit power (Ik" * 3 * Unom)

Subtransient short-circuit current

Peak short-circuit current (kappa * 2 * Ik")

network impedance at the node

R/X ratio at the node

 

Branches

name        

from        

to        

type        

tk max        

Ik">        

Imax        

Ik"<        

Name

Name of node

Name of node

Indicates whether the branch is a transformer

Maximum admissible short-circuit time

Maximum occurring short-circuit current in the branch with a fault close to the "From" node

Maximum continuous short-circuit current, LV side (only stated with transformers)

Maximum occurring short-circuit current in the branch with a fault close to the "To" node

 

 

Details

Calculate | Results | Details is used to give detailed information on selected nodes and branches in a form.

If several nodes and/or branches are selected, Previous and Next can be used to show the other nodes and branches.

 

If no IEC 60909 calculation is carried out for the node, the fault symbol is absent, and only Unom is given for the node.

 

If an IEC 60909 calculation is carried out for a single node, all element and branch currents are given.

 

If no IEC 60909 calculation is carried out for the branch, the fault symbol is absent.

 

If an IEC 60909 calculation is carried out for only one node, the branch current is given in A.

 

With transformers, the greatest continuous short-circuit current Imax (LV-side) is also given. Imax may be less than Ik"> or Ik"<. The latter currents relate to the connecting cables of the transformer.

 

Graph node

Results | Graph | General can be used to display Ik" and Ip for the selected nodes and branches in a bar chart.

The nodes and branches in the graph are sorted as indicated.

At the end of the bar, the short-circuit current of the node or branch is listed when Marks is checked. The colour is taken from the current drawing colour.

If a bar of the bar chart is clicked, the object is selected and the screen focuses on the object.

 

Export

Almost all calculated results can be exported to Excel. In fact, the export is a fixed format report of all objects on two sheets: nodes and branches.

 

See also: