Protection for Stedin: Result

<< Click to Display Table of Contents >>

Navigation:  Calculations > Protection > Protection for Stedin >

Protection for Stedin: Result

The results are aggregated by object and presented in detail in tabular form via the "Details" button in the detail results form of nodes and cables/lines.

The results can also be exported to Excel.

 

The calculation reports on seven problems:

Not switched off

Margin too small

Not selective

Causes overloading

Not disconnected, on refusing

Not selective, on refusing

Causes overload, on refusing

 

Details of all short circuits are reported on:

Fault distance: simulated fault distance (%) in the fault object (if cable or line)

Fault type: simulated short circuit

Fault resistance: fault resistance (Ohm) of the simulated short circuit

Refusing: any refusing circuit breaker

Not disconnected: whether the short circuit is not completely disconnected

Margin too small: whether the current through any tripping protection is only barely (less than 20%) greater than the minimum set current

Not selective: whether the short circuit is not selectively tripped

Causes overload: whether any branch is thermally overloaded or current overloaded during or after the short circuit, respectively

 

Color indication

Nodes, cables and lines are displayed with the color Too High if there is a problem.

The colors can be defined in the Options, under Calculation | General.

 