Remaining capacity

<< Click to Display Table of Contents >>

Navigation:  Calculations >

Remaining capacity

The remaining capacity calculation provides insight into the maximum still connectable PV or load per node.

For this purpose, several network load calculations are done: one of the current situation and several in which the test element with varying power is added. In all network load calculations, the evening and afternoon situations are calculated.

The change in load rate or voltage is calculated for each object. Only deterioration is considered, in order to ignore already existing overshoot far from the respective node.

Deterioration is:

U,after greater than 1.005*U,before

U,after less than 0.995*U,before

dU,after greater than 1.05*dU,before

load rate,after greater than 1.02*load rate,before

 

Calculation

 

Select the nodes to be calculated.

Start the calculation with Calculate | Special | Remaining capacity.

 

The calculations for PV and load are performed separately. The combination is not calculated.

The tested power ranges from 0 to 10 MW. First in steps of 1 MW, then further in steps of 0.1 MW.

 

 

Results

Results are per node:

Premaining,PV

Premaining,load

 

The options for viewing the results are:

in the diagram

in Calculate | Results | Details

 

Scheme

For nodes, the two lines are the remaining powers of PV and load.

The color of the nodes has a meaning after performing a calculation. The colors can be set in the Options with Calculation | General. The limits can be set in Calculation | Limits. The default color is shown in parentheses below.

 

Nodes

Standard (black): no particulars

Too high color (red): the PV or load yet to be connected is less than or equal to 0.1 MW.

Much too high color (dark red): the PV and load yet to be connected are both less than or equal to 0.1 MW.

Island color (green): no voltage

 

 

Calculate | Results | Details

Of selected nodes, the two result values are displayed.