<< Click to Display Table of Contents >> Navigation: Calculations > Normal Open Point optimization > General |
The normal open point optimization module calculates alternatives for the location of the normal open point in a feeder. The procedure starts from a cable with a Normal Open Point at one side. Alternative locations for the normal open point are evaluated. All the possible branches in the same feeders are evaluated until a node with 4 or more connected branches has been encountered or after six cables have been evaluated.
The objective of the normal open point optimisation is to minimise the power loss.
The constraints on the voltage level and current loading are taken into account.
The optimisation will be performed for all Normal Open Points within the network.